AS-i 3.0 Command Interface Commands of the Command Interface
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
39
4.4.11 Get transm.err.counters (GET_TECA)
With this call the error counters of all single slaves/A-slaves can be read (see
chapter: Advanced Diagnostics for AS-i Masters in the manual of your AS-i Mas-
ter).
With every reading out of the counts, the error counters will be restarted.
The counts are being read out via the corresponding host interface and will be de-
leted with every read access. The counter´s value is limited to 254. 255 will cause
a counter overflow.
The counts could be independent of the counters, which are displayed in the dis-
play of the gateway.
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
162
16
2T result
In order to get the real number of transcription errors, multiply the value with 2
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
163
16
2T – circuit
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
163
16
2T result
3APF
4slave 1A
……
34 slave 31A