Operating Instructions Safety Switch CES-AP-C.2-CH
9
Electrical connection
Warning!
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (OA and OB) must always be evaluated.
Ì The monitoring output OUT must not be used as a safety output.
Ì Lay the connection cables with protection to prevent the risk of short cir-
cuits.
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì The device generates its own clock signal on the output lines OA/OB. A 
downstream control system must tolerate these pulses, which may have a 
length of up to 0.4 ms. 
No pulses are output when the safety outputs are switched off.
Ì The inputs on an evaluation unit connected must be positive-switching, as the 
two outputs on the safety switch deliver a level of +24 V in the switched-on 
state.
Ì All the electrical connections must either be isolated from the mains supply 
by a safety transformer according to IEC 61558-2-6 with limited output volt-
age in the event of a fault, or by other equivalent isolation measures (PELV).
Ì For use and operation as per the   requirements, a power supply with the 
feature "for use in class 2 circuits" must be used. The same requirement ap-
plies to the safety outputs.
Alternative solutions must comply with the following requirements:
a) Electrically isolated power supply unit with a max. open-circuit voltage of 30 
V/DC and a limited current of max. 8 A.
b) Electrically isolatedpower supply unit in combination with fuse as per UL248. 
This fuse should be designed for max. 3.3 A and should be integrated into 
the 30 V/DC voltage section.
Ì For use and applications as per the requirements of  , a connection cable 
listed under the UL category code CYJV2 or CYJV must be used and the fol-
lowing requirements met: The connection cables of EUCHNER meet these 
requirements. The same requirement applies to the safety outputs.
Ì All electrical outputs must have an adequate protective circuit for inductive 
loads. The outputs must be protected with a free-wheeling diode for this pur-
pose. RC interference suppression units must not be used.
Ì Power devices which are a powerful source of interference must be installed 
in a separate location away from the input and output circuits for signal pro-
cessing. The cable routing for safety circuits should be as far away as pos-
sible from the cables of the power circuits.
Ì In order to avoid EMC interference, the physical environmental and operating 
conditions at the installation site of the device must comply with the require-
ments according to the standard EN 60204-1:2006, section 4.4.2 (EMC).
Ì Please pay attention to any interference fields in case of devices such as fre-
quency converters or induction heating systems. Observe the EMC instruc-
tions in the manuals from the respective manufacturer.