AS-i Safety Output Relay with four standard inputs
Address Assignment
Subject to reasonable modifications due to technical advances Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG
17
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
6. Address Assignment
The device offers two different types of AS-i addresses:
The safety relevant (single) AS-i address is the target address for the device
through which it receives the signal for the safe release of the output. This ad-
dress is not used for communication; the device only uses it to listen to ongoing
communications.
This address can only be programmed if the switch is set to PRG.
The device uses the non-safety relevant (A/B) AS-i address to communicate with
the master in order to exchange diagnostics data (I1 …I3, 1.Y1) and control sig-
nals (Alarm LED).
This address can only be programmed if the switch is set to RUN.
6.1 Programming of the safety relevant AS-i address
1. Set device switch to PRG.
2. Set desired address by using the hand-held addressing device or AS-i Mas-
ter.
3. Check programmed address by using the hand-held addressing device or
AS-i Master.
4. Check slave’s ID code by using the hand-held addressing device or AS-i
Master. The code should be set to “F”.
5. Check slave’s ID1 code by using the hand-held addressing device or AS-i
Master. Code should be the same as the tens-digit of the address.
6. Check slave’s ID2 code by using the hand-held addressing device or AS-i
Master. The code should be the same as the ones-digit of the address.
7. Check slave’s IO code by using the hand-held addressing device or AS-i
Master. The code should be “7”.
8. If the settings in steps 3 to 7 were correct continue with step 9. Otherwise
repeat, starting with step 1.
9. Set the switch on the device to RUN.
.
6.2 Programming of the non-safety relevant AS-i address
This address can be programmed by using the hand-held addressing device or
AS-i Master when the switch is set to RUN.
Warning!
The correct safety function of the device must be verified once installed within the pro-
tected machinery!